Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04BU02662
Parcel: 12907006S

Address:
1563 E 36TH ST

Review Status: Completed

Review Details: REVISION

Permit Number - T04BU02662
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/10/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Architect or Engineer must stamp slide submittal showing their review of shop drawings.
2) Provide structural calculations for structure including, footings, stairs, and raillings. Include seismic and wind analysis.
3) Handrail hgt needs to be specified per the 2003 IBC.
4) Clarify a 4: sphere cannot pase between railing openings.
10/11/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a design for the slide pumping system sealed by an Arizona registrant. Reference Section 103.2.2, UPC 1994.
2. Show that the design of the suction outlets for the slide pumping system complies with the requirements of Section 11, ANSI/NSPI - 1 2003 for entrapment avoidance.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/14/2005 GBONILL1 OUT TO CUSTOMER Completed
10/14/2005 SUE REEVES REJECT SHELF Completed