Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T04BU02662
Review Name: REVISION
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/10/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Architect or Engineer must stamp slide submittal showing their review of shop drawings. 2) Provide structural calculations for structure including, footings, stairs, and raillings. Include seismic and wind analysis. 3) Handrail hgt needs to be specified per the 2003 IBC. 4) Clarify a 4: sphere cannot pase between railing openings. |
10/11/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a design for the slide pumping system sealed by an Arizona registrant. Reference Section 103.2.2, UPC 1994. 2. Show that the design of the suction outlets for the slide pumping system complies with the requirements of Section 11, ANSI/NSPI - 1 2003 for entrapment avoidance. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/14/2005 | GBONILL1 | OUT TO CUSTOMER | Completed |
10/14/2005 | SUE REEVES | REJECT SHELF | Completed |