Permit Review Detail
Review Status: Completed
Review Details: REVISION - GRADING
Permit Number - T04BU02627
Review Name: REVISION - GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/22/2007 | DAVID RIVERA | ZONING | REVIEW | Denied | 08/20/07 Development Services Department Zoning Review Section David Rivera Principal Planner Comments: 1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan at this time. 2. The revised grading plan does not indicate the required access ramp at the disabled parking space access aisle. draw and label the access ramp per the approved site plan. |
| 08/22/2007 | ANDREW CONNOR | NPPO | REVIEW | Denied | Submit a copy of the approved landscape plan for reference. The grading application will be reviewed for compliance only when the approved documents are included in the submittal. |
| 10/01/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | This grading plan revision cannot be approved as submitted. 1. Provide a revised hydraulic analysis providing the following . a. Show that the sidewalks and other pedestrian routes will be flood free for up to a 10 year event. b. Show that sufficient freeboard will be provided for the flows to prevent flooding of any structure during a 100-year event. c. Show that positive drainage will be provided from all structures. 2. Revise the grading plan to clearly indicate drainage patterns. Show where the parking areas discharge stormwater. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/08/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 10/08/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 10/08/2007 | DELMA ROBEY | REJECT SHELF | Completed |