Permit Number: T04BU02618
Parcel: 14029014A

Address:
3381 E GLOBAL LP

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T04BU02618
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2005 Andrew Connor NPPO REVIEW Approv-Cond
01/19/2005 DOUG WILLIAMS ENGINEERING REVIEW Denied SUBJECT: Iron Mountain - Grading plan review
REVIEWER: Doug Williams
DATE: 19 January 2005
ACTIVITY NUMBERS: T04BU02618

SUMMARY: Engineering Division has reviewed the subject Grading and Private Utility and Stormwater Pollution Prevention Plans, and Geotechnical Engineering Report. Approval is not recommended at this time. Please address the following comments at a minimum:

1. The 6" Bleed-off pipe depicted in the retention/detention basin may not be approved as proposed. If the intent is to provide the required threshold retention volume in the south water harvesting area alone, the report and grading plan must demonstrate that this volume be conveyed to, and contained their respective areas during the 5-year storm event.
2. Please include a signed copy of the owner/operator certification in the SWPPP text.
3. Provide a signed/dated copy of the NOI as forwarded to ADEQ.
4. Reference the appropriate BMP for the stabilized construction entrance.
5. Please address and depict a concrete washout location on the plan.
6. Identify/label a temporary sediment basin if intended to be incorporated into this site development.
7. Add a note stating that the operator shall report to ADEQ any noncompliance (including spills) which may endanger human health or the environment. The operator shall orally notify the office listed below within 24 hours:
Arizona Department of Environmental Quality
1110 W. Washington, 5th floor (5515B-1)
Phoenix, AZ 85007
Office (602) 771-4466 Fax (602) 771-4505

Please submit three (3) sets of revised grading and stormwater pollution prevention plan/text plans addressing all comments provided above.

**A floodplain use permit will be required for the required erosion hazard setback bank protection prior to, or in conjunction with grading permit issuance**

If you have any questions, I can be reached at 791-5550, extension 1189 or Doug.williams@tucsonaz.gov

Doug Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
12/27/2004 Peter McLaughlin ZONING REVIEW Denied Site plan approval required prior to grading plan approval.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/21/2005 BETH GRANT OUT TO CUSTOMER Completed
01/21/2005 SUE REEVES REJECT SHELF Completed