2939 W SALVIA DR

Review Status: Completed

Review Details: GRADING

Permit Number - T04BU02506
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2004 Andrew Connor NPPO REVIEW Approv-Cond
11/05/2004 Doug Williams ENGINEERING REVIEW Denied 1. Correct cross section callouts A and B to reflect the proper sheet where the section locations are depicted (G2, not G-1).
2. Provide additional detail(s) for the proposed swale(s) designed for acceptance/conveyance of flow from the south, fully labeled and dimensioned, with notation for any material (hand placed rock riprap?) to be installed.
3. Revise General Grading Note # 2 to specify grading conformance with Development Standard 11-01.0.
4. Provide a note for minimum compaction requirements in all fill areas on the plan, and reference any/all applicable geotechnical recommendations.
5. Indicate on the plan proposed slope treatment for all cut/fill slopes.
6. Omit reference to top/bottom of wall elevations on the eastern (mid) property line, as there appears to be no wall proposed on this lot.

Please note that the plan may serve as a site/grading plan for permit issuance and approval purposes, once appropriately titled. The consultant may wish to contact the Zoning Review Section reviewer for any additional (site plan) notes, calculations, content requirements that must be provided on the plan.

If you have any questions, please feel free to contact me at 791-5550 ext. 1189 or via email at Dwillia1@ci.tucson.az.us

Doug Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
City of Tucson
11/10/2004 David Rivera ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/16/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
11/16/2004 ANGIE SHOFFSTALL REJECT SHELF Completed