Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - GRADING ALL
Permit Number - T04BU02490
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/06/2004 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | DATE: December 6, 2004 TO: Russell Wise, Rick Engineering Company SUBJECT: Pantano Gardens, Grading Plan REVIEWER: Loren Makus ACTIVITY NUMBER: T04BU02490 SUMMARY: The Grading Plan was reviewed by Development Services Department Engineering Division. It was not approved at this time. Grading Plan comments: 1. As previously commented, the grading plan cannot be approved until the development plan has been approved. Provide a copy of the approved development plan with the grading permit application. 2. As previously commented, the grading plan proposed grading onto adjacent properties. Provide notarized letters granting permission for all off-site work from the adjacent property owners. 3. Clarify sections E/3 and F/3 that show only the existing retaining wall. The plan view (sheet 2) indicates a screen wall will be installed in these locations. 4. Clarify section D/3. This section indicates that the extruded curb will be supporting the toe of the slope. Indicate whether a small reveal will be provided on the back of the curb to contain sloughing that may occur. 5. Provide wheel stops in parking spaces that abut sidewalk or landscape areas or provide additional space for vehicle overhang. 6. Show that the basins will be graded to drain to one location. 7. Indicate that all retaining walls including the wall in the drainage basin will be by separate permit. The wall application must include a geotechnical evaluation of the design's suitability for use in an area that is periodically inundated. Drainage Report Comments: 8. Provide in the drainage report, results of percolation tests showing that the retained volume will be disposed of within 12 hours. SWPPP Comments: 9. Show the receiving waters in the general location map in figure 1 on page 5 of the SWPPP. Revise the Grading Plan to address these comments and submit three copies of the grading plan for review. Submit two copies of the SWPPP and two copies of the revised drainage report. If you would like to meet with me to discuss any of these comments please call me at (520) 791-5550 ext. 1161 or email me at loren.makus@tucsonaz.gov. Loren Makus, E.I.T. Senior Engineering Associate Engineering Division Development Services |
| 12/08/2004 | Andrew Connor | NPPO | REVIEW | Denied | Submit approved development plan including landscape and NPPO plans to continue review. |
| 12/20/2004 | David Rivera | ZONING | REVIEW | Denied | December 20, 2004 Development Services Department Zoning Review Section David Rivera Senior Planner Comments: 1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. In addition to the approved and stamped tentative plat copies, two copies of the approved and stamped landscape and NPPO plans must be included with grading plan. 3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped tentative plat and landscape plans. 4. Please insure that the grading plan matches the concept and design of the tentative plat. Revise the grading plan to match the tentative plat or revise the tentative plat to match and comply with the grading plan. I acknowledge that changes occur at time grading plan submittal but in this case the tentative plat has not been approved and therefore changes to either plan can be made for consistency. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/22/2004 | DELMA ROBEY | OUT TO CUSTOMER | Completed |