11/09/2004 Loren Makus ENGINEERING REVIEW Denied To: Paul Keesler, P. E. DATE: November 16, 2004
Stantec Consulting Engineers
2753 S. Wilmot Road
Tucson, Arizona 85745
SUBJECT: Pad 3 at Safeway Plaza
Grading Plan T04BU02466 (First Review)
T14S, R15E, Section 30

RESUBMITTAL REQUIRED: Grading Plan, Drainage Report and Floodplain Use Permit.

The Grading Plan (GP), Drainage Report (DR) and Floodplain Use Permit (FUP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:
1. Include a response letter to the comments along with the corrected copies of the GP.
2. Provide a copy of the approved development plan with the grading permit application. Include a copy of the approved drainage report.
3. Submit the floodplain use permit with the grading permit application so they can be reviewed concurrently.
4. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
5. List all Cut and Fill quantities in cubic yards. If both are 0 cy, please list.
6. Show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, add a general note indicating sidewalk scuppers (per COT/SD) will be used when the roof scuppers locations have been designed.
7. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.

Drainage report:
1. Submit the Drainage Report with the next submittal.
2. Show the project address on the cover of the Drainage report.

Flood Plain Use Permit:
1. Submit the Drainage Report with FUP on the next submittal.



If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov

Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
c/2753 s Wilmot road grad
11/18/2004 Andrew Connor NPPO REVIEW Approved Submit approved / stamped development plan to continue review.
11/23/2004 David Rivera ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/24/2004 BETH GRANT OUT TO CUSTOMER Completed
11/24/2004 SUE REEVES REJECT SHELF Completed