Permit Number: T04BU02461
Parcel: 14125005C

Review Status: Completed

Review Details: GRADING

Permit Number - T04BU02461
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2004 Laith Alshami ENGINEERING REVIEW Denied Laith Alshami, 11/01/2004, Grading Plan and SWPPP comments:

1- Provide Block #4 dimensions and bearings. Show how the Block ties into the basis of bearing.
2- Add a General Note for Blue Staking the project before any excavation work.
3- Revise Grading Note #8 to reference Development Standard 11-01.0 (Excavation and Grading) instead of Chapter 36 of the IBC.
4- Label all streets as public or private.
5- Identify the rectangular shapes in the bottom of both recreation (detention) areas on sheet 2 of 2.
6- The detention basin inlets should incorporate sediment traps. Show on the plan the locations of the proposed detention basins sediment traps.
7- Show and label the proposed detention basins Maintenance Access Ramps.
8- Detail 8/1 does not match detail 1/11 on the Tentative Plat and it is missing relevant dimensions.
9- Show within the Recreation Areas the proposed structures including all relevant construction details and dimensions.
10- Show the slope ratios for all slopes on the outer perimeter of Sycamore Park Blvd.
11- Detail 2/1 shows different elevations from detail 2/20 on the Tentative Plat.
12- The rock rip rap dimensions in detail 2/1 do not match the dimensions shown in detail 2/20 on the Tentative Plat. Revise as necessary. Please be advised that It has been the City's experience with grouted riprap that 4" thick grout does not provide durable protection. It cracks and deteriorates easily, which can require the owner to provide continuous and costly maintenance. We recommend using a minimum of 8" grout for D50 = 6" riprap.
13- Detail 7/1 does not match the corresponding detail on the Tentative Plat. Revise the detail to include all relevant information.
14- The dimensions of the proposed riprap shown in detail 3/1 is not consistent with the information in detail 2/1. Revise.
15- The dimensions of the proposed riprap shown in detail 5/1 is not consistent with the information in detail 4/1. Revise.
16- Detail 6/1 does not match detail 14/8 on the Tentative Plat and may be missing relevant information and dimensions that could be useful for construction purposes.
17- Provide the recreation (detention) areas dimensions to facilitate their construction.
18- Submit a soils report that addresses slope protection and required setbacks from the proposed detention basins.
19- Please be advised that the Grading Plan is a construction plan, which should include all relevant information (bearings, dimensions, elevations, details, etc.) that allow the construction of the project.
20- Resubmit the redlined plan with future Grading Plan submittals.
21- Provide a detailed response letter with the next submittal that explains how the comments were addressed and references the exact locations/sheets where the revisions were made.

SWPPP Comments:

The Stormwater Pollution Prevention Plan (SWPPP) is acceptable.
10/27/2004 Andrew Connor NPPO REVIEW Denied Submit copies of the approved tentative plat plan including landscape and native plant preservation plans. Review of the plans will commence upon receipt of the requested documents.
11/16/2004 David Rivera ZONING REVIEW Denied November 16, 2004

Development Services Department
Zoning Review Section

David Rivera
Senior Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Copies of the approved and stamped tentative plat must be submitted with the grading plan package.

3. Zoning will re-review the grading plan for compliance with the approved tentative plat and grading requirements on the next submittal.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/18/2004 DELMA ROBEY OUT TO CUSTOMER Completed