Permit Review Detail
Review Status: Completed
Review Details: GRADING
Permit Number - T04BU02409
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/25/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | DATE: October 25, 2004 ACTIVITY NUMBER: T04BU02409 PROJECT NAME: Grading Plan for Navabi 4-plex PROJECT ADDRESS: 1509 East Hedrick Drive PROJECT REVIEWER: Patricia Gilbert The following items must be revised or added to the grading plan. Please include a response letter with the next submittal that states how all comments have been addressed. RESUBMITTAL REQUIRED: GRADING PLAN 1. Revise General Grading Note number 8 to read, "All work shall conform to Grading Standards DS 11-01." 2. Show roof drainage (flow arrows). DS 2-02.2.1.A.16. 3. Basis of Bearing is not required. Remove General Grading note number 1. 4. Give the field book and page for the Basis of Elevation. 5. There is a significant difference in the basis of elevation between the site plan and the grading plan. A difference of 96.18' does not seem possible. Revise the Basis of Elevation on the Grading Plan. |
| 10/25/2004 | Andrew Connor | NPPO | REVIEW | Approv-Cond | |
| 11/23/2004 | David Rivera | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/24/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |