Permit Review Detail
Review Status: Completed
Review Details: GRADING
Permit Number - T04BU02308
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/21/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Denied | Grading Plan 1. Indicate cut and fill quantities on plan. 2. All lettering and dimensions shall be the equivalent of twelve (0.12") point or greater in size. The purpose of this requirement is to assure that all lettering is legible when reviewed and will maintain that legibility when reproduced and photographically reduced (microfilmed) for record-keeping purposes. D.S. 2-05.2.1.C Text too small, correct and revise. 3. Sidewalk area next to building cannot be flushed with asphalt. Indicate finish grades for top of curb and top of pavement or finish grade. Correct and revise grades for the asphalt/sidewalk area next to building. 4. Indicate a legend to identify symbols. 5. Arrows too small. Correct size. |
| 09/23/2004 | Andrew Connor | NPPO | REVIEW | Denied | Site plan approval is necessary to continue review. |
| 10/04/2004 | DAN CASTRO | ZONING | REVIEW | Denied | grading plan may not be approved until it has been approved by the Engineering Section. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/04/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 10/04/2004 | TAMI ACHONG | REJECT SHELF | Completed |