Permit Number: T04BU02308
Parcel: 111041760

Review Status: Completed

Review Details: GRADING

Permit Number - T04BU02308
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2004 BLANCA ESPINO ENGINEERING REVIEW Denied Grading Plan
1. Indicate cut and fill quantities on plan.

2. All lettering and dimensions shall be the equivalent of twelve (0.12") point or greater in size. The purpose of this requirement is to assure that all lettering is legible when reviewed and will maintain that legibility when reproduced and photographically reduced (microfilmed) for record-keeping purposes. D.S. 2-05.2.1.C Text too small, correct and revise.

3. Sidewalk area next to building cannot be flushed with asphalt. Indicate finish grades for top of curb and top of pavement or finish grade. Correct and revise grades for the asphalt/sidewalk area next to building.

4. Indicate a legend to identify symbols.

5. Arrows too small. Correct size.
09/23/2004 Andrew Connor NPPO REVIEW Denied Site plan approval is necessary to continue review.
10/04/2004 DAN CASTRO ZONING REVIEW Denied grading plan may not be approved until it has been approved by the Engineering Section.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/04/2004 TAMI ACHONG OUT TO CUSTOMER Completed
10/04/2004 TAMI ACHONG REJECT SHELF Completed