Permit Number: T04BU02256
Parcel: 134051430

Review Status: Completed

Review Details: OTHER

Permit Number - T04BU02256
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS


1) Show how the tables on sheets 2,9, and 19 and the calc`s provided relate to
each other. Highlight the values for this project at all the tables provided.
2) Provide connection design and analysis. Sheets 1,2,3, and 4 shows something
Regarding connections, but is not specific as to which connectors are being re-
referred to. On calc`s specify connection being designed. How do the tables
On sheets 3 and 4 used?
3) Provide a complete site plan. Clarify! Show proposed structure and existing.
Label buildings and show all dimensions. Define property lines on site plan.
4) Reference and cross-reference all details to plans and/or other details.
10/13/2004 Terry Stevens BUILDING-RESIDENTIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/20/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
10/20/2004 ANGIE SHOFFSTALL REJECT SHELF Completed