Review Details: RESUBMITTAL - GRADING ALL
Permit Number - T04BU02197
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/24/2004 | DOUG WILLIAMS | ENGINEERING | REVIEW | Denied | 1. Revise or modify General Grading Note 1B to specify/clarify that the maximum time for disposal allowed for the detention/retention basin is 12 hours, in accordance with Development Standard 10-01.3.5.1.3 a. 2. Include specific language under General Grading Note 1 to assure conformance to the Geotechnical Engineering Evaluation recommendations for 3' of engineered fill on Lot 1. The SWPPP is acceptable and may be stamped for approval upon completion and addressing of the above comments on revised grading plans. Please include three (3) sets of revised grading plans and the two SWPPP's currently in the package, upon resubmittal. If you have any questions, please contact Elizabeth Eberbach, P.E., or Doug Williams, Sr. Engineering Associate at 791-5550 ext. 2204 or 1189, respectively. |
| 12/02/2004 | David Rivera | ZONING | REVIEW | Denied | December 2, 2004 Development Services Department Zoning Review Section David Rivera Senior Planner Comments: 1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering Review Section. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/03/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 12/03/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |