Permit Number: T04BU02065
Parcel: 14117005A

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T04BU02065
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2004 LOREN MAKUS ENGINEERING REVIEW Denied DATE: December 7, 2004
TO: Kent Delph, Delph Engineering, Inc.
SUBJECT: Ace Commons, Grading Plan
REVIEWER: Loren Makus
ACTIVITY NUMBER: T04BU02065

SUMMARY: The Grading Plan and Stormwater Pollution Prevention Plan were reviewed by Development Services Department Engineering Division. They were not approved at this time.

Grading Plan comments:
1. The grading permit cannot be approved until the tentative plat has been approved. Additional comments may be forthcoming once the tentative plat has been approved
2. Revise the detail for the Refuse Enclosure Detail to provide the required 10' by 10' clear dimension between the pipe post barricades at the sides. (See redlines) (DS 6-01.4.2.C)

Stormwater Pollution Prevention Plan
3. Update the SWPPP if any changes are required by any changes in the grading plan.

Revise the Grading Plan to address these comments and submit three copies of the grading plan for review. Submit two copies of the revised SWPPP .If you would like to meet with me to discuss any of these comments please call me at (520) 791-5550 ext. 1161 or email me at loren.makus@tucsonaz.gov.

Loren Makus, E.I.T.
Senior Engineering Associate
Engineering Division
Development Services
12/07/2004 Andrew Connor NPPO REVIEW Approved PROVIDE COPIES OF THE APPROVED TENTATIVE PLAT, LANDSCAPE PLAN, AND NATIVE PLANT PRESERVATION PLANS. ADDITIONAL COMMENTS WILL APPLY UPON REVIEW OF THOSE PLANS.
12/07/2004 Andrew Connor NPPO REVIEW Approved Plans have been included.
12/23/2004 CRAIG GROSS ZONING REVIEW Approved approved per tentative plat S04-115

Final Status

Task End Date Reviewer's Name Type of Review Description
12/28/2004 ANGIE SHOFFSTALL OUT TO CUSTOMER Completed