Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04BU01979
Parcel: 140420420

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T04BU01979
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2004 Andrew Connor NPPO REVIEW Denied Site plan approval is necassary to continue review.
10/21/2004 Loren Makus ENGINEERING REVIEW Denied DATE: October 25, 2004
TO: OPW Engineering, LLC
SUBJECT: Commercial Parking Lot, Site Plan and Grading Plan Review
REVIEWER: Loren Makus
ACTIVITY NUMBERS: T04CM03684 and T04BU01979

SUMMARY: The Site Plan and Grading Plan were reviewed by Development Services Department Engineering Division. The Site Plan, Grading Plan and Stormwater Pollution Prevention Plan (SWPPP) were not approved at this time.
Site and Grading Plan comments:
1. As previously commented, show how water will be directed to the retention/detention basin. Clarify in the details how water will enter the basin. If the pavement in the adjacent PAAL is to be flush with the top of the walls, this should be shown in the details. Also make a note that the retaining walls will be built under separate permit. (DS 2-02.2.1.A.16)
2. Provide details of the basin to show the ground surface on each side of the weir and stabilization at the weir outlet. Provide enough detail so the inspectors can confirm that the outlet is constructed according to plan.
SWPPP comments:
3. Revise the SWPPP to be consistent with the Site/Grading plan in the matter of import or export. The SWPPP still indicates that the site is designed to balance.
4. Part IV.J.1. Each Operator must sign the SWPPP

Revise the Site Plan, Grading Plan and the SWPPP to address all of these comments and resubmit three copies of the grading plan and the SWPPP. If you would like to meet with me to discuss any of these comments please call me at (520) 791-5550 ext. 1161.

Loren Makus, E.I.T.
Senior Engineering Associate
Engineering Division
Development Services
10/25/2004 Peter McLaughlin ZONING REVIEW Denied Site plan approval required.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/28/2004 TAMI ACHONG OUT TO CUSTOMER Completed
10/28/2004 ANGIE SHOFFSTALL REJECT SHELF Completed