Permit Number: T04BU01950
Parcel: 103210240

Review Status: Completed

Review Details: RESUBMITTAL - GRADING

Permit Number - T04BU01950
Review Name: RESUBMITTAL - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2004 Andrew Connor NPPO REVIEW Denied 1. Submit approved tentative plat. Final plat was included with previous submittal

2. Clearly define the grading limits on Sheet 5 of grading plan within Common Area C, A 30' SCZ must be maintained revise plan(s) as necessary per DS 2-07.2.2.B.4
10/11/2004 Doug Williams ENGINEERING REVIEW Denied SUBJECT: Silverbell Vista Grading/Paving/SWPPP Review
REVIEWER: Doug Williams
DATE: 14 October 2004
ACTIVITY NUMBER: T04BU01950
T13S, R13E, Section 33

Resubmittals Required: Three sets of Revised Grading, Paving and Stormwater Pollution Prevention Plans. One copy/set of the stamped/approved Tentative Plat and Landscape/NPPO plan.

SUMMARY: Approval of the subject plans is not recommended at this time. Paving/sewer plans were not included in the resubmittal package. Please address all comments listed below in a response letter and on revised plans, and assure the resubmittal contains all of the items listed above.

GRADING PLAN:

1. Provide the revised paving (and sewer) plan as a part of this grading plan/permit application.
2. Depict the project basis of elevation (benchmark) location on plan view, and provide the elevation datum in General Note 1.
3. Depict a minimum 2' setback from property line in Section 6/3.


STORMWATER POLLUTION PREVENTION PLAN (SWPPP):

1. Please provide a copy of the signed/dated Notice of Intent (NOI) as forwarded to Arizona Department of Environmental Quality (ADEQ).
2. Provide the required operator signatures/dates on page 12 of each text.

If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us.

Douglas Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
10/21/2004 David Rivera ZONING REVIEW Denied October 21, 2004

Development Services Department
Zoning Review Section

David Rivera
Senior Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Draw and label the street sidewalks and include acees ramps where required.

3. Per the Grading Plan title block there is to be numerous Common Areas beginning with Common Area "A" and ending with Common Area "L". Per the the approved Tentative Plat title block three common areas were proposed. Please clarify if the title block for the grading plan is correct or if the developer has decided to add additional or re-classify some of the common areas. If so the CC&R's must be amended to include the new common area designations and maintenance requirements. The CC&R's will have to be re-recorded.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/08/2004 TAMI ACHONG OUT TO CUSTOMER Completed
12/08/2004 ANGIE SHOFFSTALL REJECT SHELF Completed