Permit Number: T04BU01784
Parcel: 11806103D

Address:
1988 W KING AV

Review Status: Completed

Review Details: OTHER

Permit Number - T04BU01784
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS

1) The soil friction of 0.25 is not permitted unless specified by the soils report.
2) Sheet 11 of calc`s shows that the unit formula is exceeded by 12% and is
not acceptable.
3) Special inspection is required.
4) The allowable soil pressure of 1500 psf. shall not be exceeded in any case.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/13/2004 LISA LESNY OUT TO CUSTOMER Completed
09/13/2004 ANGIE SHOFFSTALL REJECT SHELF Completed