Permit Number - T04BU01784
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/27/2004 | Raul Palma | BUILDING-COMMERCIAL | REVIEW | Denied | City of Tucson, Development Services BUILDING AND STRUCTURAL COMMENTS 1) The soil friction of 0.25 is not permitted unless specified by the soils report. 2) Sheet 11 of calc`s shows that the unit formula is exceeded by 12% and is not acceptable. 3) Special inspection is required. 4) The allowable soil pressure of 1500 psf. shall not be exceeded in any case. |