Permit Number: T04BU01740
Parcel: Unknown

Review Status: Completed

Review Details: GRADING

Permit Number - T04BU01740
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2004 Joseph Linville NPPO REVIEW Denied Submit a copy of the approved Tentative Plat and associated landscape and native plant preservation plans. The grading plans will be reviewed for code compliance and consistency with the approved plans.
08/05/2004 Loren Makus ENGINEERING REVIEW Denied DATE: August 9, 2004
TO: Rick Engineering Company
SUBJECT: Pepper Viner at Rita, Grading Plan
REVIEWER: Loren Makus
ACTIVITY NUMBER: T04BU01740

SUMMARY: The Grading Plan and Stormwater Pollution Prevention Plan (SWPPP) were reviewed by Development Services Department Engineering Division. The Grading Plan and SWPPP were not approved at this time.

Grading Plan comments:
1. The Grading Plan cannot be approved until the Tentative Plat has been approved. Additional comments may be forthcoming with submittals after the Tentative Plat has been approved. All of the outstanding issues that remain from the most recent Tentative Plat Review must be resolved.
a. Differential Grading.
b. Street layout
c. Percolation test results
2. Revise the lot numbers to agree with the Tentative and Final Plats.
3. Provide general dimensions for the basins and drainage structures.
4. Show the security barrier in Sction J/3.
5. Revise the callout for section H/4 on sheet 2. Show project boundary line in section H/3 and clarify that there will be no cut or fill slopes within the outer 2 feet of the project site. Make sure that the property line as shown in the detail agrees with the plan view.
Stormwater Pollution Prevention Plan
6. Provide a location map for this project. The included location map appears to be for a project in a different jurisdiction.
7. Update the plan for any changes made in the grading plan.

Revise the Grading Plan and SWPPP to address these comments and resubmit two copies of each for review. If you would like to meet with me to discuss any of these comments please call me at (520) 791-5550 ext. 1161 or email me at loren.makus@tucsonaz.gov.

Loren Makus, E.I.T.
Senior Engineering Associate
Engineering Division
Development Services
08/22/2004 DAVID RIVERA ZONING REVIEW Denied August 22, 2004

Development Services Department
Zoning Review Section

David Rivera
Senior Planner

Comments:


1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering and Landscape Review Section and approval of the site plan.

2. Two copies of the approved and stamped tentative plat, landscape and NPPO plans must be included with grading plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/23/2004 BETH GRANT OUT TO CUSTOMER Completed
08/23/2004 ANGIE SHOFFSTALL REJECT SHELF Completed