Permit Number: T04BU01621
Parcel: 11501155E

Address:
2350 N 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T04BU01621
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2004 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: November 8, 2004
ACTIVITY NUMBER: T04BU01621
PROJECT NAME: Sahuaro Apartments
PROJECT ADDRESS: 2350 North 6th Avenue
PROJECT REVIEWER: Patricia Gilbert

The following items must be revised or added to the grading plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: GRADING PLAN (Three copies)
SWPPP APPROVED

1. A copy of the stamped approved Site Plan must be included with the Grading Plan submittal.

2. The Site Plan is currently in review. Any changes made to the Site Plan must be reflected on the Grading Plan. The Site Plan and Grading Plan must match.

3. Submit three copies of the grading plan with the next submittal. The purpose of this is one copy goes to records, one copy to the Engineering Inspectors and one goes back to the customer.

4. The SWPPP is approved. Please submit three copies of the grading plan with the next submittal.
11/16/2004 Andrew Connor NPPO REVIEW Denied Site plan approval by all the reviewing agencies is necessary to continue review.
12/01/2004 David Rivera ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2004 LISA LESNY OUT TO CUSTOMER Completed
12/02/2004 ANGIE SHOFFSTALL REJECT SHELF Completed