Permit Number: T04BU01547
Parcel: 116094240

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T04BU01547
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2004 Andrew Connor NPPO REVIEW Denied Submit approved tentative plat including landscape and NPP plans to continue review.
08/31/2004 Loren Makus ENGINEERING REVIEW Denied SUBJECT: Montage Vista Lots 36-45
REVIEWER: Loren Makus
DATE: 2 September 2004
ACTIVITY NUMBERS: T04BU01547

SUMMARY: Engineering Division has reviewed the grading plan. This review is to be considered a courtesy review, and upon approval will serveas a master, or reference document for individual lot grading plan submittals. Approval is not recommended at this time. Please address the following comments in a response letter and include
indication in the letter of the sequence of lots to be graded:

1. Please refer to Section 13.1 of the 2000 International Building Code (IBC) for placement of fill in excess of 2 feet above existing grade at any location in the outer 100 feet of a developing site. The proposed grading for lots 36-39, 41and 42 indicate placement of fill in excess of 2' above existing grades. Demonstrate conformance with the requirements outlined in the above-noted section, with provision of the necessary documentation, written permission and any mitigation plan information, with a resubmittal, where applicable (IBC Ch.36, Section 13.1). Clearly show that all of the requirements have been met.
a. Provide a copy of the written permission obtained from the Director or his assignee. The written permission must approve the engineering justification.
b. Provide complete property owner notification, which must include the engineering justification, the Director's appoval letter and the names and addresses of the developer and the engineer of record.
c. Show that the adjacent neighbors have approved the required mitigation plan.
2. Include the drainage flow arrows in the legend.
3. As previously commented, depict all lot discharge locations and provide wall opening notes, or details for each location. Include any proposed erosion protection measures, fully labeled and dimensioned.
4. Provide a copy of a standard soils/geotechnical report including all setback, grading, slope, interceptor swale and terracing recommendations, at a minimum.

Resubmittal shall include 2 copies of a revised grading plan addressing all comments provided above, and a copy of the geotechnical report.

Loren Makus, E.I.T.
Sr. Engineering Associate
Engineering Division
Development Services Department
09/11/2004 David Rivera ZONING REVIEW Denied September 11, 2004

Development Services Department
Zoning Review Section

David Rivera
Senior Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering and Landscape Review Section and until all zoning comments or concerns have been addressed.

2. Two copies of the CDRC approved and stamped tentative plat, landscape and NPPO plans must be included with grading plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/14/2004 BETH GRANT OUT TO CUSTOMER Completed
09/14/2004 ANGIE SHOFFSTALL REJECT SHELF Completed