Review Details: GRADING

Permit Number - T04BU01455
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2004 Paul Machado ENGINEERING REVIEW Denied To: Intertect Architectual DATE: June 28, 2004
Steve Shields
6089 E. Grant Road
Tucson, Arizona 85712

SUBJECT: Modular Bldg. for Tag Elementary School, 10129 E. Speedway Blvd.
Grading plan T04BU01455 (First Review)
T14S, R15E, Section 2

RESUBMITTAL REQUIRED: Grading Plan and Drainage Statement.

The Grading Plan (GP) and Drainage Statement (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Please include a response letter to the comments along with the corrected copies of the GP.
2. The grading plan cannot be approved prior to the approval of the Site plan.
3. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17.
4. Show Grading plan number (T04BU01455) on all sheets
5. The grading differential for this project exceeds the 2.0-foot allowed in Section 13 of the 2000 IBC. Please proceed with the notification process in Section 13 for mitigation.

Drainage Statement:
1. A Drainage Statement is required. A DS is a brief description of drainage conditions applicable for a site which is not affected be 100-year flows of 100 cfs, or more, and is neither subject to detention requirements nor impacted by flows from a significant watercourse per S.M.D.D.F.M., chap. II, 2.1.3.
2. The content and format of the DS should follow S.M.D.D.F.M., chap. II, 2.1.3.
3. Show the project address on the cover of the Drainage Statement.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office, (520) 879-8010 fax, C:/10129 E. Speedway Bldg. grad_modular
06/28/2004 Andrew Connor NPPO REVIEW Denied Submit approved site plan to continue review.