Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE ONLY

Permit Number - T04BU01382
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2004 JIM EGAN FIRE REVIEW Passed
10/27/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
11/19/2004 LOREN MAKUS ENGINEERING REVIEW Approved
11/29/2004 Christy Foreman BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 11-30-04
ACTIVITY NUMBER: T04BU01382
PROJECT NAME: METAL RAMADA
PROJECT ADDRESS: 618 E. 20TH ST.
ARCHITECT / ENGINEER: INCITE ARCHITECTS
PROJECT REVIEWER: CHRISTY FOREMAN



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) PLEASE CLARIFY OCCUPANCY OF EACH BLDG. ON SITE AND TYPE OF CONSTRUCTION.
2) DIMENSION SEPERATION BETWEEN BLDGS. DIMENSION BLDGS. PROVIDE CODE ANALYSIS FOR ALL BLDGS ON SITE TO JUSTIFY ALLOWABLE SQUARE FOOTAGE.
3) PROVIDE DETAIL OF 3/8" CABLE WITH TURNBUCKLE CONNECTION TO ROOF FRAMING ON SHT. A2.
4) PROVIDE DETAIL PURLIN / BEAM CONNECTION ON SHT A2. PROVIDE CALCULATIONS THAT WELD WILL HOLD FOR UPLIFT CONDITION.