Permit Number: T04BU01365
Parcel: 134234110

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE ONLY

Permit Number - T04BU01365
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2004 JIM EGAN FIRE REVIEW Approved
07/29/2004 Christy Foreman BUILDING-COMMERCIAL REVIEW Denied PLAN REVIEW COMMENTS PROJECT #T04BU01365
07/30/2004 6320 E. Broadway

1. Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response
STRUCTURAL PLANS:
1. Clarify piece E to A weld. Special Inspection for field welds.
2. Per calculations ½" dia. bolt required. Drawings show bracket to rafter attachment at 3/8".
3. Text should be larger on details for archiving. 10 pt. minimum.
If you have any questions, please contact your assigned plans examiner Christy Foreman at 791-5550, extension 1108.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/11/2004 BETH GRANT OUT TO CUSTOMER Completed
08/11/2004 SUE REEVES REJECT SHELF Completed