Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE ONLY
Permit Number - T04BU01365
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/06/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/29/2004 | Christy Foreman | BUILDING-COMMERCIAL | REVIEW | Denied | PLAN REVIEW COMMENTS PROJECT #T04BU01365 07/30/2004 6320 E. Broadway 1. Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response STRUCTURAL PLANS: 1. Clarify piece E to A weld. Special Inspection for field welds. 2. Per calculations ½" dia. bolt required. Drawings show bracket to rafter attachment at 3/8". 3. Text should be larger on details for archiving. 10 pt. minimum. If you have any questions, please contact your assigned plans examiner Christy Foreman at 791-5550, extension 1108. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/11/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |
| 08/11/2004 | SUE REEVES | REJECT SHELF | Completed |