Permit Number: T04BU01198
Parcel: 111063100

Review Status: Completed

Review Details: GRADING

Permit Number - T04BU01198
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2004 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: May 24, 2004
ACTIVITY NUMBER: T04CM00843
PROJECT NAME: Lecocq Apartments
PROJECT ADDRESS: 3118 East Blacklidge Blvd.
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the grading plan. Please include a response letter with the next submittal that states how all comments have been addressed. To compare plans please include the second submittal set of plans with the third submittal.

RESUBMITTAL REQUIRED: GRADING PLAN

1. The Site Plan is currently in review. Any changes made to the Site Plan must be reflected on the Grading Plan. The Site Plan and Grading Plan must match.

2. A copy of the stamped approved Site Plan must be included with the Grading Plan submittal.

3. Sidewalks must be flood free for up to the 10-yr. event. Add a note to the plan, "All roof down spouts on all structures must be routed under any adjacent sidewalk." DS 2-08.4.1.E

4. Detail 2 and 3 on sheet C2 is dimensioned with an architectural scale. For consitancy change to an engineering scale.

5. Add a legend to the grading plan. Show what indicates existing elevation and finish grades.

6. Show the depth of the water harvesting areas in the landscape border. Either by a general note or label on the plan.

7. Dimension from street centerline to the existing curb and the proposed sidewalk. DS 2-02.2.1.A21.

8. Show roof drainage. DS 2-02.2.1A.

9. Sheet C2 detail 2 and 3 depicts a swale adjacent to the property line. The minimum setback for the top of a cut or fill slope is two feet. This swale is too close to the property line. Revise the grading plan to show the required setbacks from the property line. Chapter 36 of the IBC.

10. Dimension the length and the width of the swales.
06/08/2004 ANDREW CONNOR NPPO REVIEW Approved
06/19/2004 DAVID RIVERA ZONING REVIEW Denied June 19, 2004

Development Services Department
Zoning Review Section

David Rivera
Senior Planner

Comments:

Two copies of the approved and stamped site plan, landscape and NPPO plans must be included with the grading plan.

Zoning will approve the grading plan upon approval of the plan by the Engineering Section.