Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2004 Andrew Connor NPPO REVIEW Denied 1. This site is subject to the provisions of:
CITY OF TUCSON DEVELOPMENT STANDARD NO. 9-04.0 HILLSIDE DEVELOPMENT SITE IMPROVEMENT including Vegetation preservation and re-vegetation per DS 9-04.3.2. Revise grading note as necessary.

2. Submit NPPO plan per DS 2-15.0.

3. Identify the limits of grading and areas of non-disturbance per DS 9-04.3.1.A.2 If natural areas are designated on a site or lot, temporary fencing will be installed where they abut construction areas in order to prevent encroachment into the natural areas

4. Note: All plants designated, as preserved-in-place shall be retained at their existing grade during and after construction. Preservation fencing per DS 2-06. Figure 1 is required to be installed beyond the "drip-line" of the vegetation by one-half (½) the distance of the "drip-line" radius. DS 2-15.6.A

5. Note: Prior to any site disturbance a pre-grading inspection is required. Inspections may be scheduled by calling the IVR system at (520) 740-6970, inspection #9015 or by calling the Landscape Field Representative directly at 791-5640 Ext. 1140.
06/30/2004 Paul Machado ENGINEERING REVIEW Denied To: Ray Graffam DATE: July 6, 2004
Owner/Applicant
8731 E. Desert Spring
Tucson, Arizona 85730
SUBJECT: 10950 E. Escalante Road
Grading Plan T04BU01116 (First Review)
T14S, R15E, Section 36

RESUBMITTAL REQUIRED: Grading Plan and Hydrology Report

The Grading Plan (GP) and Hydrology Report (HR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:The Grading Plan cannot be reviewed or approved prior to an approved Site Plan.
1. The content and format of the Site Plan should follow D. S. 2-02.0.

Hydrology report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. A Hydrology report is required for parcels affected by 100 year flows of 100 cfs, of more per S.M.D.D.F.M., chap. II, 2.1.2.
3. The content and format of the Hydrology report should follow S.M.D.D.F.M., chap. II, 2.1.3.
4. Show the project address on the cover of the Hydrology report.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
08/03/2004 David Rivera ZONING REVIEW Denied August 3, 2004

Development Services Department
Zoning Review Section

David Rivera
Senior Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering and Landscape Review Section and approval of the site plan.

2. Two copies of the approved and stamped development/site plan, landscape and NPPO plans must be included with grading plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/03/2004 DELMA ROBEY OUT TO CUSTOMER Completed