Permit Number - T04BU01098
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2004 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied 1. Provide architectural plans for proposed use(s). Include complete floor plan.
2. Revise special inspection notes to include all items requiring special inspection i.e.: epoxy bolts, expansion bolts etc.
3. Plans to include special inspection of shear wall (SW1) to verify existing condition complies with calculations. Please note that the inspection is to be done prior to demolition.
4. Provide tributary load of west roof load. Please clarify in calculations.