Permit Number: T04BU01059
Parcel: Unknown

Address:
10411 E BILBY RD

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T04BU01059
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2004 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, 06/22/2004

Grading Plan Comments:

1- Submit a copy of the Soils Report to support the proposed slope protection and to verify the definition of "Steep Slopes".
2- Therse is still a concern that lots 15-21 may still be impacted by the street runoff in the superelevated streets.
3- There is still a Cross sections J/11 shown near lots 17 & 18. Revise.
4- The proposed trail and multi purpose path locations should be determined and shown on the Tentative Plat and Grading Plan.
5- Provide a copy of the revised Tentative Plat with the next Grading Plan submittal.
6- Provide a detailed response letter with the next submittal that explains how the comments were addressed and references the exact locations/sheets where the revisions were made.


SWPPP Comments:

The Stormwater Pollution Prevention Plan is acceptable and it is hereby approved.
06/23/2004 Andrew Connor NPPO REVIEW Denied 1. Submit approved tentative plat including landscape and NPPO plans to continue review.

2. This development is subject to the provisions of the scenic corridor zone. A separate review and approval is required. TCC 23A-42

3. Provide limits of grading including natural areas such as scenic corridor zones and areas of non-disturbance per LUC 2.8.2.6

4. Approval of Plant/Habitat Inventory and mitigation plan for disturbed areas per TCC Chapter 29 Article VIII prior to grading plan approval
07/07/2004 PATRICIA GEHLEN ZONING REVIEW Denied July 7, 2004

Development Services Department
Zoning Review Section

David Rivera
Senior Planner

Comments:

Two copies of the CDRC approved and stamped tentatative plat, landscape and NPPO plans must be included with grading plan with the next grading plan submittal.

Zoning will review and approve the grading plan once the Engineering and Landscape review sections have approved the grading plan.