Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04BU00770
Parcel: 12801003A

Address:
240 S WILMOT RD

Review Status: Completed

Review Details: POOL:COMM-MODEL

Permit Number - T04BU00770
Review Name: POOL:COMM-MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Show the source of makeup water to the spa and pool.
2. Show the means of waste disposal for the filtration system.
3. Provide natural gas pipe sizing calculations. Include gas pressures and developed pipe lengths on plans. Reference Section 1217.0, UPC 1994 with AZ State amendments.
4. Provide a hose bibb with a vacuum breaker, to be used for washing down the entire pool deck.
5. Revise the pool circulation pipes to limit the water velocity to less than 6 feet per second for suction piping.
6. Provide a plumbing plan of the revised equipment room (water and waste).
7. Provide deck drainage and show how site drainage is being controlled.
04/01/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide plans sealed by an Arizona Registrant.
2. Provide plans, drawn to a reasonable scale, that demonstrate compliance with the provisions of the Pool and Spa Code, 1996. The minimum font size shall be 10 points. Reference Section 302.2, Uniform Administrative Code, 1997.
3. Show the method of venting the pool and spa heaters and the provisions for combustion air.
4. Show the rated capacities of the spa and pool pumps in GPM at the design head.
04/09/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Denied 1) Provide a site plan along with plans.
04/14/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied T04BUOO770 DENIED 4/14/04
1. Provide plans sealed by an Arizona Registrant.
2. Provide plans, drawn to a reasonable scale, that demonstrate compliance with the provisions of the National Electrical Code, 1999. The minimum font size shall be 10 points. Reference Section 302.2, Uniform Administrative Code, 1997.
3. See the attached sheet for Electrical Permit Requirements.
04/20/2004 CAGUILA1 ZONING REVIEW Needs Review