Permit Number: T04BU00623
Parcel: 11005314C

Address:
3175 N SWAN RD

Review Status: Completed

Review Details: GRADING

Permit Number - T04BU00623
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2004 Paul Machado ENGINEERING REVIEW Denied To: Steve Gregor, P. E. DATE: April 12, 2004
Gregor and Grenier Engineering Inc.
1660 N. Avernon Way
Tucson, Arizona 85712
SUBJECT: Camp Lowell Corner, 3191 N. Swan Road
Grading Plan T04BU00623 (First Review)
T14S, R15E, Section 28

RESUBMITTAL REQUIRED: Grading Plan, Drainage Report and SWPPP

The Grading Plan (GP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Please include a response letter to the comments along with the corrected copies of the GP.
2. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
3. A Flood Plain Use permit will be required for any work done within the Creekside Wash.
4. Two different addresses are being used for this project, which address is correct?
5. Please add a note to the GP regarding the waiver of the Ret./Det. Basin by the property owner downstream.
6. If the project is to be phased, each phase must function independently of the future phases. If so, please designate the phase lines.
7. The refuse containers located in a P.A.A.L. shall be designed using a 30 degree angle per D.S. 2-02.2.1.32 and D.S. 6-01.0. Please provide a detail of the refuse enclosure also.
8. Please show a typical cross section of the P.A.A.L.
9. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
10. Please edit note 14 of the "Grading and Paving Notes" to reflect the following. Generally slopes of 2H: 1V or greater require hand placed w/ fabric or grouted riprap.
11. Please add a grading note: Cut or fill slopes require a 2' minimum setback from property line per Section 13 of the 2000 IBC.


Drainage report:
1. A provision for the notarized letter from the property owner was made in report, but the letter was not inserted into the report. Please correct.

Stormwater pollution prevention plan:
1. The SWPPP is accepted. Please provide (3) copies of the SWPPP package upon re-submittal of the GP.

If you have any questions, I can be reached at 791-5550 x1193 or pmachad2@ci.tucson.az.us
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
04/12/2004 David Rivera ZONING REVIEW Denied Approved and stamped development/site plan must be included with grading plan.

Zoning will review and approve the grading plan upon final approval by the Engineering section.
04/12/2004 Andrew Connor NPPO REVIEW Denied Submit approved development plan including landscape and NPPO plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/13/2004 EGRANT1 OUT TO CUSTOMER Completed
04/13/2004 ANGIE SHOFFSTALL REJECT SHELF Completed