Permit Number: T04BU00566
Parcel: 110060760

Review Status: Completed

Review Details: GRADING

Permit Number - T04BU00566
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2004 Paul Machado ENGINEERING REVIEW Denied To: Integrated Design & Construction DATE: April 5, 2004
Norman Amy
6401 N. Camino Catrina
Tucson, Arizona 85718

SUBJECT: 3943 E. Monte Vista Drive
Site plan T04BU00566 (First Review)
T13S, R14E, Section 34

RESUBMITTAL REQUIRED: Grading Plan

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:
1. Grading plan clearly marked "GRADING PLAN". The title "Utility and Drainage plan" should be called out as a grading plan.
2. Please include a response letter to the comments along with the corrected copies of the GP.
3. The Grading plan cannot be approved prior to the approval of the site plan.
4. List administrative address/site address on plans.
5. Provide a Location Map (3" = 1 mile)
6. Show all symbols on a legend.
7. Call out surface paving material.
8. Curb and Gutter elevation include drainage flow with percent slope.
9. Show details of all surface materials.
10. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
11. Show the 100-year flood peak discharge.
12. Cut or fill slopes require a 2' minimum setback from property line.
13. All proposed fill to conform to Section 13 of the 2000 IBC - Address grade differential of proposed lot grades from the existing buildings adjacent to the graded site - 2' minimum setbacks from top and toe or cut of fill slopes.
14. Drainage patterns with percent slopes (Show patterns within the first 100 feet from the property line).
15. Flow arrows, grades and flow rates within and adjacent to site to show drainage scheme.
16. Call out peak discharges entering and exiting the site.

Drainage report:
1. A Drainage Statement has accepted by the Engineering/Floodplain Department.


If you have any questions, I can be reached at 791-5550 x1193 or pmachad2@ci.tucson.az.us
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
04/08/2004 Joseph Linville NPPO REVIEW Denied Submit an approved site plan, including landscape and native plant preservation plans. They plans are required before our review can proceed.
04/10/2004 DAVID RIVERA ZONING REVIEW Denied Approved and stamped development/site plan must be included with grading plan.

Zoning will review and approve the grading plan upon final approval by the Engineering section.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/13/2004 LISA LESNY OUT TO CUSTOMER Completed
04/12/2004 SUE REEVES REJECT SHELF Completed