Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04BU00501
Parcel: 137105040

Address:
5530 S 12TH AV

Review Status: Completed

Review Details: GRADING

Permit Number - T04BU00501
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2004 PETER MCLAUGHLIN ZONING REVIEW Denied Site plan approval required.
04/01/2004 Andrew Connor NPPO REVIEW Denied Revise grading plan in conjunction with site plan comments.
04/02/2004 LOREN MAKUS ENGINEERING REVIEW Denied DATE: April 2, 2004
TO: Metro Permit Express
SUBJECT: Site Plan and Grading Plan, Family Dollar, 5530 S. 12th Avenue
REVIEWER: Loren Makus
ACTIVITY NUMBER: T04CM01015 and TO4BU00501

SUMMARY: The Site Plan, Grading Plan and Drainage Report were reviewed by Development Services Department, Engineering Division on April 2, 2004. They were not approved. Please address the following comments.

Site Plan/Grading Plan Comments:
1) There appears to be a differential grading violation near the loading zone. Show that there will be less than two feet of fill within the outer 100 feet of the project. Otherwise meet the requirements of the grading ordinance.
2) Provide clear grading limits on the grading plan.
3) Provide estimated cut and fill quantities.
4) A letter from City of Tucson Environmental Services will be required to approve alley service for solid waste pickup.
Drainage Report
5) As indicated in the drainage report, provide results of the percolation tests. Demonstrate that the retained volume will percolate within 12 hours.

Revise the Site Plan, Grading Plan and Drainage Report to address all of these comments and resubmit two copies of each for review. Include a letter explaining how each comment has been addressed.

Loren Makus
Senior Engineering Associate
Engineering Division
Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
04/05/2004 LISA LESNY OUT TO CUSTOMER Completed
04/05/2004 SUE REEVES REJECT SHELF Completed