Permit Number: T04BU00463
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T04BU00463
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2004 Joseph Linville NPPO REVIEW Approv-Cond LANDSCAPE INSPECTOR MUST CHECK FENCING OF NATURAL AREAS PRIOR TO GRUBBING OR GRADING.
05/18/2004 DAVID RIVERA ZONING REVIEW Denied Zoning will not approve until Engineering approves plan.
05/18/2004 Loren Makus ENGINEERING REVIEW Denied The grading plans must be sealed and signed by a Registered Professional Engineer.
Correct the typical lot detail on sheet 6 to provide an actual number.
Revise the SWPPP to provide sediment controls at the inlets to the low flow pipes from the basins.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/07/2004 DELMA ROBEY OUT TO CUSTOMER Completed