03/09/2004 Loren Makus ENGINEERING REVIEW Denied DATE: March 11, 2004
TO: Dan White, Physical Resource Engineering
SUBJECT: A-Atlas, Grading Plan and Stormwater Pollution Prevention Plan Review
REVIEWER: Loren Makus
ACTIVITY NUMBER: T04BU00396

SUMMARY: The Grading Plan and Stormwater Pollution Prevention Plan (SWPPP) were reviewed by Development Services Department Engineering Division. The Grading Plan and SWPPP were not approved at this time.

Grading Plan comments:
1) The grading plan cannot be approved until the site plan has been approved.
2) Add a note indicating that grading will be performed in accordance with IBC 2000 Chapter 36.
3) Provide general dimensions for the retention basin.
4) Provide additional details (elevations) for the basin outlet structure and for the alley crossing.
5) Show means for preventing unauthorized vehicle access into the retention basin.

SWPPP Comments

Provide three copies of the SWPPP with the next submittal. I recommend revising the description of the receiving waters on pages 7 and 8. Swan Park Wash is a tributary of Naylor Wash.
Revise the Grading Plan to address all of these comments and resubmit two copies for review along with a copy of the approved site plan. If you would like to meet with me to discuss any of these comments please call me at (520) 791-5550 ext. 1161.

Loren Makus
Senior Engineering Associate
Engineering Division
Development Services
03/16/2004 Joseph Linville NPPO REVIEW Denied Submit revised plans. No comments at this time.
03/17/2004 DROBEY1 ZONING REVIEW Needs Review