Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2004 JOE LINVILLE NPPO REVIEW Denied Submit an approved development plan including landscape and native plant preservation plans.
03/12/2004 Loren Makus ENGINEERING REVIEW Denied DATE: March 12, 2004
TO: Stantec Consulting
SUBJECT: West Point Crossing Shops A, Grading Plan Review
REVIEWER: Loren Makus
ACTIVITY NUMBER: T04BU00332

SUMMARY: The Grading Plan was reviewed by Development Services Department Engineering Division. The Grading Plan was not approved at this time.

Grading Plan comments:
1) The grading plan cannot be approved until the development plan has been approved. Include a copy of the stamped approved development plan with your resubmittal. Additional comments may be made after the development plan has been approved.
2) The solid waste container location is not accessible as shown. Provide an accessible location for the solid waste container. If the accessibility will be provided with the development of the adjacent lot, show cross access easement recordation information. A certificate of occupancy will not be issued until accessibility is provided.
3) Revise the section callouts on Sheet C1.02 to refer to the correct page for the details.
4) Provide barriers as described in City of Tucson Development Standard 3-05.2.3.C to prevent parked vehicles from extending over the property line.
5) Revise Grading & Drainage Note 3 to indicate that all grading conform to IBC 2000 Chapter 36.

Revise the Grading Plan to address all of these comments and resubmit two copies for review along with a copy of the approved development plan. If you would like to meet with me to discuss any of these comments please call me at (520) 791-5550 ext. 1161.

Loren Makus
Senior Engineering Associate
Engineering Division
Development Services
03/23/2004 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
3/23/2004
Zoning will review and approve the grading plans once Engineer has approved.