Permit Number - T04BU00252
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2004 Paul Machado ENGINEERING REVIEW Denied To: William Strang, P.E. DATE: April 7, 2004
PRE Engineering,Inc.
4655 N. Flowing Wells
Tucson, Arizona 85705
SUBJECT: Desert Villa Care Ctr., 250 S. Volack Lane
Grading Plan T04BU02949 (Second Review)
T14S, R15E, Section 28

RESUBMITTAL REQUIRED: Grading Plan.

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Please include a response letter to the comments along with the corrected copies of the GP.
2. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information. It appears that a fair amount of rip-rap is being constructed off-site in Wrightstown Wash. Permits will be required for any work off-site also a FUP will be required for placing the rock rip-rap within the flood plain limits.
3. Provide the EHS symbol in the Legend.
4. Show proposed grade breaks. Are there grade breaks at either of the other entrances?
5. 10-year runoffs and roof drainage must be conveyed through scuppers underneath sidewalks. Verify compliance with this requirement. The flows in the 10-year event tend to be greater, therefore sidewalk scupper are warranted. An example of a grading note follows: If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations or drainage crossing the sidewalks, have been designed and located will suffice.
6. Demonstrate positive drainage in the bottom of the detention basin to prevent nuisance ponding. Per previous comment. Please dimension the basin as much as possible. A detail may apply in the instance. This comment ensures proper construction and is used for inspection purposes.
7. Submit a soils report, which addresses proposed slope stabilization. Per the Soils report and a note on the grading plan indicating slope treatment:
· All slopes at 3:1 require re-vegetation per the soils report (typ.).
· All slopes at 2:1 require rip-rap, D50=6" with filter fabric.
· All slopes at 1:1 require grouted rip-rap or a retaining wall.
8. Provide a construction detail for the refuse enclosure. The clear area of the inside of the enclosure is 10' square. With the guard post 2' from the wall, the enclosure doe not meet this standard.

Drainage report:
1. All the comments have been addressed. The DR has been accepted.

Stormwater pollution prevention plan:
1. In sight of the area of disturbance, 0.91 acres, a SWPPP is not required.

If you have any questions, I can be reached at 791-5550 x1193 or pmachad2@ci.tucson.az.us
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
04/08/2004 Joseph Linville NPPO REVIEW Denied Submit copies of the landscape and native plant preservation plans approved with the development plan. Ensure that the grading plan is revised to include a disturbance limit line that corresponds with the Native Plant Preservation Plan.
04/10/2004 DAVID RIVERA ZONING REVIEW Denied Approved and stamped development/site plan must be included with grading plan.

The development plan submitted with the grading plan was never submitted for site plan aprroval and stamps. A site card will site plan approval stamps on the development plan is required prior to final approval.

Zoning will review and approve the grading plan upon final approval by the Engineering section.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/28/2004 TAMI ACHONG OUT TO CUSTOMER Completed
04/12/2004 SUE REEVES REJECT SHELF Completed