Permit Review Detail
Review Status: Completed
Review Details: GRADING
Permit Number - T04BU00205
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/26/2004 | Patricia Gehlen | ZONING | REVIEW | Approved | |
| 02/27/2004 | DOUG WILLIAMS | ENGINEERING | REVIEW | Denied | SUBJECT: Lindeman Residence - Grading Review REVIEWER: Doug Williams DATE: 27 February 2004 ACTIVITY NUMBERS: T04CM00349 & T04BU00205 SUMMARY: Engineering Division has reviewed the Site/Grading plan received on 27 January 2004. Approval is not recommended at this time. Please address the following comments: GRADING PLAN COMMENTS 1. Provide a general grading note specifying conformance to the 2000 International Building Code - local amendment (Chapter 36 - Excavation and Grading). This document may be accessed at: http://www.ci.tucson.az.us/dsd/2000_IBC_Amendments.pdf 2. Provide geotechnical report with recommendations addressing earthwork, setbacks, slope stability/treatment and drainage for the site. 3. Please omit either the "existing topo to be modified" or the "proposed topo" from the legend and the corresponding delineations on the plan. Preferably, depict "existing" and "proposed" topo/contours. 4. Provide a basis of elevation with reference to City of Tucson (COT) Field Book and Page; 5. Provide the recording information (Bk 49 Pg 35) for the private drainage easement. 6. Depict and label the 10' Public Utility Easement, as shown on the Final Plat for Tohono Ridge, with recording information (Bk 51 Pg 89). 7. Provide a minimum of one northwest - southeast cross section. Please include the driveway, property line, existing curb and sidewalk locations, and indicate the elevation increments, fully labeled and dimensioned on all cross-sections, at a minimum. 8. Observation of current photo-topography indicates area drainage may enter this site currently, and that upon construction of the driveway entrance, there may be an increase in such if cutting the curb, as noted (if the existing curb is 2' wedge curb, remove the note for cutting of the curb). Provide proposed spot elevations or clearly depict proposed contours on the plan in this area, demonstrating drainage will be accommodated and conveyed around the proposed home. Area drainage must be discharged in a fashion similar or identical to existing conditions, without diverting flow to adjacent property. 9. Remove the "+/-" symbol from all elevations 10. The grading limits and callout arrow provided are not clear. Please insure the limits of grading are very clear on a revised plan. If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us. Doug Williams Sr. Engineering Associate Engineering Division Development Services Department |
| 02/27/2004 | Andrew Connor | NPPO | REVIEW | Denied | 1) Native Vegetation Disturbance Plan included in original Tohono Ridge Tentative Plat states the mitigation of (7) 15-gal Cecidium mycrophyllum (Foothills Palo Verde) for Lot 22. Submit Site Plan with placement of trees. 2) Note on site plan: Revegetation of disturbed areas will use Upland Seed Mix which includes: Botanical Name Common Name / lbs/acre Encelia farinosa (P, C/W) Brittlebush / 1.5 Ambrosia (Franseria) deltoidea (P, C) Triangle-Leaf Bursage / 4.0 Larrea tridentata (divaricata) (P, W) Creosote Bush, Greasewood / 4.0 Acacia constricta (P, W) Whitethorn Acacia, Mescat / 2.0 Cercidium floridum (P, W) Blue Palo Verde / 2.0 Acacia greggii (P, W) Cat's Claw Acacia / 2.0 Sphaeralcea ambigua (P, C/W) Desert Globe-Mallow / .5 Baileya multiradiata (P, C/W) Desert Marigold / 1.0 3) Revise comment on site plan to reflect: All exposed exterior walls and roofs of structures, retaining walls, and accessory structures, except satellite dishes, shall be earth tone in color and will blend with the predominant natural colors found on the lot or parcel. LUC 2.8.1.8.C |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/02/2004 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 03/02/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |