Permit Number: T04BU00203
Parcel: 116272250

Review Status: Completed

Review Details: RESUBMITTAL - GRADING

Permit Number - T04BU00203
Review Name: RESUBMITTAL - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2004 Loren Makus ENGINEERING REVIEW Denied The grading plan cannot be approved until the Fire Department Examiner has approved the site plan. Revise the site/grading plan to account for the Fire Examiner's comments. Adjust the cut and fill quantity as necessary.
06/08/2004 Andrew Connor LANDSCAPE REVIEW Denied 1. Provide calculation for mitigation of native plants per Eagles View Landscape Concept Plan dated January 11,1993 or submit separate NPP plan per DS 2-15.0

2. Note: Fencing shall be required during construction for all undisturbed plans and natural desert areas per DS 2-6.0 Figure-1


3. Note: Prior to any site disturbance a pre-grading inspection is required. Inspections may be scheduled by calling the IVR system at (520) 740-6970, inspection #9015 or by calling the Landscape Field Representative directly at 791-5640 Ext. 1140.
06/21/2004 DROBEY1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/29/2004 DELMA ROBEY OUT TO CUSTOMER Completed