Permit Number: T04BU00202
Parcel: 205630240

Review Status: Completed

Review Details: GRADING

Permit Number - T04BU00202
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/20/2004 Paul Machado ENGINEERING REVIEW Denied To: Joseph Smith
Golden Star Properties
8727 E. Golf Links Road
Tucson, Arizona 85730

SUBJECT: 11361 E.Placita Rancho Grande
Grading Plan T04BU00202 (First Review)
T14S, R15E, Section 36

RESUBMITTAL REQUIRED: Grading Plan, Drainage Report and SWPPP

The Grading Plan (GP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:
1. Please include a response letter to the comments along with the corrected copies with re-submittal.
2. Grading plan clearly marked "GRADING PLAN". Please remove any reference on the plans to the site plan. This review was done for grading only.
3. Please include a copy of the tentative plat for review. Additional comments may be forth coming upon the receipt of the tentative plat.
4. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
5. List administrative address/site address on plans.
6. Provide a Location Map (3" = 1 mile), with the pertinent information.
7. Call out surface paving material.
8. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
9. Call out the names of all washes.
10. Call out all slopes and stabilization material (concrete, riprap, gabbions or vegetation).
11. Slopes of 3H: 1V require hand placed riprap.
12. Cut or fill slopes require a 2' minimum setback from property line.
13. Flow arrows, grades and flow rates within and adjacent to site to show drainage scheme.
14. All easement of record must be graphically shown on the plan together with recording docket and page per D.S. 2-02.2.1.20.
15. Please show the area of open cluster space per the final plat in a surveyable manor.



Drainage Statement:
1. A DS is required for parcels not affected by 100 year flows of 100 cfs, of more per S.M.D.D.F.M., chap. II, 2.1.3.
2. The content and format of the DS should follow S.M.D.D.F.M., chap. II, 2.1.3.
3. Please show project address on cover sheet of DS.


If you have any questions, I can be reached at 791-5550 x1193 or pmachad2@ci.tucson.az.us
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
02/23/2004 DAVID RIVERA ZONING REVIEW Denied zoning cannot approve the grading plan until the Engineering section has reviewed and approved the plan.
02/25/2004 Andrew Connor NPPO REVIEW Approved Exception: LUC 3.8.3.4.A Lot recorded 10-17-95

Final Status

Task End Date Reviewer's Name Type of Review Description
04/06/2004 LISA LESNY OUT TO CUSTOMER Completed
02/27/2004 ANGIE SHOFFSTALL REJECT SHELF Completed