Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04BU00161
Parcel: 106022070

Address:
107 W PASTIME RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04BU00161
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/26/2004 JIM TATE ENGINEERING REVIEW Denied DATE: February 26, 2004
ACTIVITY NUMBER: T04BU00161
PROJECT NAME: Earlybird Subdivision
PROJECT ADDRESS: 107 W. Pastime
PROJECT REVIEWER: James C. Tate, P.E., CFM

The following items must be revised or added to the Grading Plan. Please include a letter with the next submittal addressing how all the engineering and floodplain comments have been addressed.

Resubmittal Required: Grading Plan

Grading Plan

1. The weir detail C-1/3 shows top opf basin at 35.4. The detail shows a seir depth of 6" and a weir invert elevation of 34.4. This would make the top of basin at 34.9. Also the plan view does not show a 35 contour around the basin. It appears that the top of basin should be 34.9.

2. Show the Grading Limits on the plan. The limits shown can barely be seen. A darker line type needs to be used. The limits must be clearly discernable.

3. Show finish grades for the driveway between lots 5 and 6.

4. Lots 5 and 6 show proposed elevations but these are outside the grading limits. These should be indicated as existing grades.

5. Specify the type of survey pins to be placed on the lot corners.
02/26/2004 PETER MCLAUGHLIN ZONING REVIEW Denied
03/16/2004 Joseph Linville NPPO REVIEW Denied Resubmittal required. Plans are acceptable for Landscape and plant preservation.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/16/2004 EGRANT1 OUT TO CUSTOMER Completed
03/16/2004 SUE REEVES REJECT SHELF Completed