Permit Number: T04BU00122
Parcel: Unknown

Address:
131 W ELVIRA RD

Review Status: Completed

Review Details: RESUBMITTAL - GRADING

Permit Number - T04BU00122
Review Name: RESUBMITTAL - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2004 Joseph Linville NPPO REVIEW Approv-Cond
09/07/2004 Doug Williams ENGINEERING REVIEW Denied SUBJECT: Desert Vista Grading, Paving and Sewer Plan review
REVIEWER: Doug Williams
DATE: 8 September 2004
ACTIVITY NUMBER: T04BU00122
T15S, R13E, Section 13

Resubmittal Required: Revised Grading, Paving & Sewer Plans and select Stormwater Pollution Prevention Plan items.

SUMMARY: Engineering Division has reviewed the subject plans. Approval is not recommended at this time. Please address the following comments prior to resubmittal.

1. The sidewalk scupper and supporting hydraulic calculations are acceptable for approval, however the omission of a basin maintenance access ramp precludes allowing approval of the grading plan. The plan must be revised accordingly, with clear depiction of an access ramp, fully labeled and dimensioned
2. Provide an invert elevation for the channel notch/basin weir tie-in to be constructed.
3. Include a note stating that a separate permit will be required for the retaining wall along the western property line.
4. Assure all revisions/modifications are reflected on the grading, paving and sewer plans, where applicable (for example, Section E-E - removable post barricades).

Stormwater Pollution Prevention Plan:

5. Provide 3 copies of the Arizona Construction General Permit (CGP).
6. Provide 3 copies of the signed Notice of Intent, as forwarded to Arizona Department of Environmental Quality (ADEQ). These may be included on the SWPPP plan sheets if preferred.
7. Please visit the following website address for additional SWPPP content requirements: http://www.azdeq.gov/environ/water/permits/download/cswppp.pdf. Assure the minimum information necessary is contained on the SWPPP's
General:

8. Please complete and submit a Floodplain Use Permit application with the resubmittal package.
*NOTE*
A Right of Way Permit/Private Improvement Agreement (PIA) will be required for all construction, excavation and sewer installation in the public right of way. Contact Permits and Codes Section - Tucson Department of Transportation (TDOT) at 791-5100 for questions or inquiries.
Resubmittal will require three (3) sets Stormwater Pollution Prevention Plans, and three (3) sets of revised Grading Paving and Sewer Plans addressing all of the comments provided above.
If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us.

Douglas Williams
Sr. Engineering Associate
Engineering Division
Development Services Department

Final Status

Task End Date Reviewer's Name Type of Review Description
09/14/2004 TAMI ACHONG OUT TO CUSTOMER Completed
09/14/2004 SUE REEVES REJECT SHELF Completed