Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04BU00122
Parcel: Unknown

Address:
131 W ELVIRA RD

Review Status: Completed

Review Details: GRADING

Permit Number - T04BU00122
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2004 Patricia Gehlen ZONING REVIEW Approved
02/17/2004 Andrew Connor NPPO REVIEW Denied Submit approved landscape and NPPO plans per S03-014.
02/19/2004 Doug Williams ENGINEERING REVIEW Denied SUBJECT: Desert Vista Grading & Stormwater Pollution Prevention plan (SWPPP) review
REVIEWER: Doug Williams
DATE: 19 February 2004
ACTIVITY NUMBER: T04BU00122
T15S, R13E, Section 13

Resubmittal Required: Grading and SWPP Plans

SUMMARY: Engineering Division has reviewed the subject plans. Approval is not recommended at this time. The following comments must be addressed prior to resubmittal:

1. Depict and label grading limits on the plan.
2. Provide the administrative address, cut/fill quantities and total area of disturbance on the plan.
3. Correct the "BLUESTAKE" telephone number provided in General Grading Note #1.
4. Provide a General Grading Note that grading shall be in conformance with the 2000 International Building Code (IBC) - local amendment (Chapter 36 - Excavation and Grading). For information, visit http://www.ci.tucson.az.us/dsd/2000_IBC_Amendments.pdf.
5. Label curb and sidewalks to be constructed to City of Tucson/Pima County Standard Details for Public Improvements, 1994 Edition (COT/PC SD) 209 and 200, respectively, in the northern portion of section C-C, and preferably in plan view on sheet 1.
6. Label all new curb access ramps to be constructed in accordance with PC/COT SD 207, with specific reference to the type or alternative to be constructed, and provide a details or details on the plans with the resubmittal. Please ensure all access ramps depicted/proposed meet the minimum requirements contained within the Standard Details for Public Improvements noted above.
7. Depict and label all curb return radii in accordance with the approved Tentative Plat.
8. Revise or omit the 2' dimension adjacent to the face of curb in the western portion of section B-B.
9. Please provide details for the removable handrail, as the COT/PC standard detail referenced does not provide for removable-type handrails.
10. Provide longitudinal street grades for the new private streets, including detailed roadway profiles with stationing. Ensure all existing and proposed sewer and water lines, storm drains and any other utilities are included. Please check that all dimensions, grades, and slopes provided are in accordance with the drainage report to ensure the 100-year floodplain limits will be contained as depicted/approved on the Tentative and Final Plats.
11. The drainage report discusses a slotted drain, catch basin(s), and an underground storm drain discharging to the retention basin. Clearly depict, label and dimension fully, all such drainage structures, with elevations provided on revised grading plans. If Public Improvement Plans are under preparation and/or review, include reference to the plans by I number on the plan.
12. Depict, label and dimension the existing channel notch and basin outlet to be constructed, and provide detailed construction drawings for the outlet construction, fully dimensioned and labeled with all elevations noted. Include a detail or details for the proposed wall openings, with clear notation of the number of openings, opening width and height, with clear depiction of this location on plan view.
13. Please provide reinforcing material to be used in the construction of the basin maintenance access ramp, in order to accommodate vehicular maintenance activity, in section D-D.
14. Please note that the approved Tentative Plat specifies 3:1 H:V basin side slopes, whereas basin A details indicate 2:1 slopes. Please revise as necessary, to conform to configuration specified in the approved drainage report, and include a note for a minimum 42" security barrier to be installed around the entire basin.
15. Provide cross sections for typical perimeter grading, and ensure a minimum 2' setback is depicted at all property lines, in accordance with Section 14 of the 2000 IBC (Chapter 36).
16. Provide a dimension for the maintenance access ramp length.
17. Please note that additional comments may be necessary upon resubmittal.
Stormwater Pollution Prevention Plan:
1. Depict and label an appropriate concrete washout location on sheet 2.
2. Please label the retention basin to be utilized as the sediment basin, as stated in item 1 of stabilization practices and controls.
3. Provide a copy of the signed and dated Notice of Intent (NOI) forwarded to Arizona Department of Environment Quality (ADEQ).
4. Depict and label a protected materials storage area on sheet 2.

***NOTE***
A right of way permit is required for any construction, excavation or development related work activity in the public right of way. Contact Permits and Codes Section, Transportation Department (TDOT) at 791-5100 for questions or inquiries.
Resubmittal will require revised Grading and SWPP plans addressing all of the comments provided above.
If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us.

Douglas Williams
Sr. Engineering Associate
Engineering Division
Development Services Department

Final Status

Task End Date Reviewer's Name Type of Review Description
02/20/2004 EGRANT1 OUT TO CUSTOMER Completed
02/20/2004 ANGIE SHOFFSTALL REJECT SHELF Completed