Permit Number: T04BU00052
Parcel: 13216647A

Review Status: Completed

Review Details: GRADING

Permit Number - T04BU00052
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2004 Doug Williams ENGINEERING REVIEW Denied SUBJECT: Federal Express Parking Grading Plan Review
REVIEWER: Doug Williams
DATE: 5 April 2004
ACTIVITY NUMBER: T04BU00052

SUMMARY: Engineering Division has reviewed the Grading Plan and Stormwater Pollution Prevention Plan/text received on 15 March 2004. Approval is not recommended at this time - previous grading plan comments are in need of clarification prior to approval of the plan. Please include a copy of approved Hydrologic and Hydraulic Report with the resubmittal. The following comments must be addressed prior to resubmittal:

Grading Plan:
1. Provide additional finish grade information south and west of basin 2, demonstrating the appropriate drainage area will drain to the detention/retention basin inlet, or provide a note to "grade unpaved area to basin inlet" or something similar, as provided for the contributing drainage area to basin 1.
2. Include inlet elevations for each basin on the plan.
3. Basin outlet weir details A and D appear to have been reversed when comparing the grading plan with the Development Plan. Please revise these details as necessary, and clarify the varying widths, to specify which outlet weir is 2.5 feet wide and which is 4 feet wide.
4. Depict and label all limits of grading on the plan.
Please address all of the above comments. Resubmittal shall include a copy of the approved Development Plan and 3 copies of the revised Grading Plan addressing the comments listed above.
If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us.

Douglas Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
04/08/2004 Joseph Linville NPPO REVIEW Denied Submit copies of the approved development plans, including landscape plans in order for review of the plans to proceed.
04/10/2004 DAVID RIVERA ZONING REVIEW Denied Zoning will review and approve the grading plan upon final approval by the Engineering section.

Approved and stamped development/site plan must be included with grading plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/12/2004 LISA LESNY OUT TO CUSTOMER Completed
04/12/2004 ANGIE SHOFFSTALL REJECT SHELF Completed