Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T04BU00027
Parcel: 107060840

Review Status: Stopped

Review Details: TANKS

Permit Number - T04BU00027
Review Name: TANKS
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2004 ANY ZONING REVIEW Stopped
01/06/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. Provide total load calculations for panel and service. Understood that there is existing equipment to be powered by the panel.
2. Show all work needed to switch existing load over to new panel.
3. Both motors shall have a disconnect per Article 430. Items on Keynotes 8 & 9 do not include motor disconnects per the One-Line Diagram and reference notes. There is no Legend or Key to Symbols to clarify.
4. Provide Legend/Key to symbols, to clarify such items as the device to be installed on the Work Shop.
5. Provide for conduit seals at the panel and the converter, because there it is not possible to provide such seal at the boundary of the Class 1 Division 2 per NEC 501-5 (b).
6. Unless Tucson Electric Power Company has explicitly stated that the AFC at this particular location does not exceed 10,000 A, please verify. According to the 2002 Service Requirements, SR-510, most RESIDENTIAL single phase services have less than 10,000 AFC if rated 200A or less, but this is commercial.
7. The #10 GND in the run to the 10 HP motor, should be #8 per NEC Table 250-122, as it its line side OCPD is rated at 70A.
8. Demonstrate compliance with NEC 455-6 (a) (2) and 455-7 (b). Can not evaluate without knowing the phase-converter nameplate current rating.
01/06/2004 ANY ENGINEERING REVIEW Stopped
07/08/2004 SREEVES1 FIRE REVIEW Stop