Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: PLUMBING
Permit Number - T03PL01214
Review Name: PLUMBING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/24/2003 | DAVE WITT | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/24/2003 | DWITT1 | WWM | REVIEW | Approved |