Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03PL01167
Parcel: 12710229A

Address:
603 N WILMOT RD

Review Status: Completed

Review Details: PLUMBING

Permit Number - T03PL01167
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/17/2003 GERRY KOZIOL WWM REVIEW Approved