Permit Number: T03PL01167
Parcel: 12710229A

Address:
603 N WILMOT RD

Review Status: Completed

Review Details: PLUMBING

Permit Number - T03PL01167
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Coordinate the size of the reduced pressure backflow preventers and the pipe manifold with the building water supply. Comply with Section610.2, UPC 1994.