Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03PL01152
Parcel: 127102290

Address:
601 N WILMOT RD

Review Status: Completed

Review Details: PLUMBING

Permit Number - T03PL01152
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Coordinate the size of the reduced pressure backflow preventers and the pipe manifold with the building water supply. Comply with Section610.2, UPC 1994.
07/17/2003 TACHONG1 WWM REVIEW Needs Review