Permit Number: T03PL00486
Parcel: 116270060

Review Status: Completed

Review Details: PLUMBING

Permit Number - T03PL00486
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Include the fixture unit requirements for the club house and pool facilities in the water calculations. Reference Section 610.1, UPC 1994.
2. Resolve the discrepancy in the number of M/H spaces: sheet P1 calls out 152 spaces but sheet P2 calls out only 151 spaces.
3. Resize the RPBP's and the water meter to comply to Section 610.2, UPC 1994.
4. Provide water connection details for the Club House, including any necessary mechanical protection of the riser. Reference Appendix E, Part C, UPC 1994.
5. Recalculate the sizes of the water distribution piping so they are capable of delivering a minimum of 12 fixture units of water to each M/H space with a maximum pressure drop (due to friction) of 1.65 PSI/ 100 feet. Reference Appendix A, Section A5, and Appendix E, Part C, UPC 1994.
6. Show mechanical protection of the exposed gas connection equipment. Reference Appendix E, Part D, Section E36, UPC 1994.
7. Recalculate the sizes of the gas distribution pipes so they are capable of delivering the required gas supply to each M/H space as calculated using the methods shown in Chapter 12, and Appendix E, Part D, UPC 1994.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/10/2003 ELAINE ROSE OUT TO CUSTOMER Completed