Review Details: FLOODPLAIN
Permit Number - T03OT02266
Review Name: FLOODPLAIN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/30/2003 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | The Hydrology Report specifies that the minimum finish floor elevation must be 2465.3 NGVD-29. This must be specified on the Site Plan. Sheet 2 specifies the FFE as 0'-00". This is incorrect. The correct FFE must be shown on the plan. Please note that the as-built finish floor elevation must be certified by a Registered Land Surveyor on the form provided with the Flood Use Permit providing proof that the floor was poured to the correct elevation. |