Permit Number: T03OT02041
Parcel: 13821030F

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T03OT02041
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2004 Andrew Connor LANDSCAPE REVIEW Approved
04/05/2004 Michael St. Paul ZONING REVIEW Denied SITE PLAN TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Michael St.Paul FOR: Patricia Gehlen
Planning Technician Principal Planner

PROJECT:
T03OT02041
334 West Los Reales Road
New Church Second Review
TRANSMITTAL: April 9, 2004
DUE DATE: April 7, 2004


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.
CODE SECTION/
DEVELOPMENT
STANDARD

1. There appears to be a lot split on this site plan dividing the eastern O-3 portion of this site from the C-1 portion of the site. The new legal description describes two (2) individual parcels and the legal description does not match the legal provided by Pima County on their web site. Provide one legal description of the entire site that matches the legal provided by the County.
LUC Sec 4.1.2
2. The maneuverability behind Class II Bicycle Parking spaces must be a minimum of five feet (5'), only four feet (4') is shown on the plan. A Class I Bicycle Parking detail must be added to the site plan and it must include how the bicycles will be secured.
DS 2-09.2.9
3. The existing sight-visibility-triangles are not the same as the future SVTs.



















If you have any questions about this transmittal, please call Michael St.Paul, (520) 791-5608.
04/05/2004 Michael St. Paul HANDICAP-SITE REVIEW Approved
04/05/2004 Andrew Connor NPPO REVIEW Approved
04/07/2004 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/15/2004 EGRANT1 OUT TO CUSTOMER Completed
04/09/2004 ANGIE SHOFFSTALL REJECT SHELF Completed